Please use this identifier to cite or link to this item: https://idr.l1.nitk.ac.in/jspui/handle/123456789/11133
Title: Experimental and finite element analysis of power transformer
Authors: Srujana, N.
Babu, R.R.
Venkataramana, K.
Issue Date: 2014
Citation: Journal of Structural Engineering (India), 2014, Vol.41, 2, pp.90-96
Abstract: Post earthquake studies have clearly shown that the seismic performance of substation is very weak and results in damage causing huge direct and indirect loss to the power utilities. Considerable time is spent to repair, retrofit or replace the damaged substation equipment and to restore power supply. Many substation equipments failed when installed in the substation due to moderate earthquake forces though these equipment were experimentally qualified. Power transformer is one of such critical equipment of substation. Vibrations due to earthquake amplified by the transformer tank causes failure in the porcelain bushings mounted on the top of the transformer tank. An attempt has been made in this study to identify resonance frequencies and corresponding damping ratios of a typical transformer by both experimental and numerical methods. In addition, ground acceleration amplification is also calculated from shake table experiments and response analysis of finite element model.
URI: http://idr.nitk.ac.in/jspui/handle/123456789/11133
Appears in Collections:1. Journal Articles

Files in This Item:
There are no files associated with this item.


Items in DSpace are protected by copyright, with all rights reserved, unless otherwise indicated.