Please use this identifier to cite or link to this item:
https://idr.l1.nitk.ac.in/jspui/handle/123456789/8140
Title: | Genetic algorithm in location identification of AEPD source: Some aspects |
Authors: | Punekar, G.S. Antony, D. Bhavanishanker, T. Nagamani, H.N. Kishore, N.K. |
Issue Date: | 2013 |
Citation: | 2013 IEEE 1st International Conference on Condition Assessment Techniques in Electrical Systems, IEEE CATCON 2013 - Proceedings, 2013, Vol., , pp.386-390 |
Abstract: | Using the experimental data obtained from an Acoustic Emission Partial Discharge (AEPD) system, efforts are made to locate the source of Partial discharge (PD) with a transformer tank. The AEPD data with 8 sensors (available in the literature) is numerically experimented with a Genetic Algorithm, although minimum of 4 sensors only are necessary for identifying the location. With eight sensors, four sensors considered at a time, form 70 ( 8C4) combination of sensors. The effect, implication and usage of superfluous sensor data in identifying the location with GA is analyzed and reported. Results are compared with Newton's method. � 2013 IEEE. |
URI: | http://idr.nitk.ac.in/jspui/handle/123456789/8140 |
Appears in Collections: | 2. Conference Papers |
Files in This Item:
There are no files associated with this item.
Items in DSpace are protected by copyright, with all rights reserved, unless otherwise indicated.